NodeBuilder Errors Guide 3-3
LCL# Description
7
The encoded value for the device's clock input of <id> is
not within the supported range of <min> to <max>
[LCL#7]
An invalid encoded clock value has been used to describe the
hardware clock speed. See LCL#2.
8
The encoded value for the channel's minimum clock rate
of <id> is not within the supported range of <min> to
<max> [LCL#8]
An invalid encoded clock value has been specified for the
channel's minimum clock speed. This value originates from the
standard transceiver database, and the presence of this
problem indicates a corrupted or incorrect database record.
Make sure your standard transceiver database (stdxcvr.xml)
has not been corrupted. An update might be available at the
www.lonmark.org website. Contact LonSupport if problem
persists.
9
Unable to compute media access control values (raw
transceiver data): the specified Neuron clock frequency is
too high for the transceiver [LCL#9]
This error condition is unavoidable for some combinations of
(typically) high Neuron clock rates and (typically) slow
channels. A different operating mode of the same transceiver or
a lower Neuron clock rate might solve the problem.