Echelon i.LON 100 e2 Internet Server Manual de usuario Pagina 23

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 223
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 22
i.LON 100 Internet Server Programmer’s Reference
Event Priority Level
Assigned
Result of Operation
Custom Application
Invokes
DataPointResetPriority
255 The custom application invokes the
DataPointResetPriority function to reset the
priority level assigned to the data point. This does
not result in a change in the data point’s value,
but the priority level assigned to the data point is
reset to 255, the lowest priority. At this point, all
applications will be able to write to the data point.
For more information on the
DataPointResetPriority function, see
DataPointResetPriority on page 3-10.
Event Scheduler Updates
Data Point
240 The Event Scheduler successfully updates the
value of the data point, as the priority level used
here (240) is greater than that assigned to the
data point by the DataPointResetPriority function.
3-6
Vista de pagina 22
1 2 ... 18 19 20 21 22 23 24 25 26 27 28 ... 222 223

Comentarios a estos manuales

Sin comentarios