CPD 3000 Integration Guide 11
Table 1 LC Network UNVTfaults Variables Implemented on the CPD 3000
Network Variable Type Notes
nviLampValue
SNVT_switch
Primary control input. The level
translates to a 0-10V control signal with
the transform being subject to the values
configure in nciControlConfig defined
below. By default, 50% results in a 5V
control signal to the ballast, driver, or,
generator controlled by the CPD 3000.
nviStatReset UNVTstatControl
Sets/initializes energy, runtime, and
error counts.
nvoControlData UNVTcontrolData
A structured variable describing all
current operating values and state of
the LC. This is described in the
following section.
nvoLampFb SNVT_switch
Feedback of the current
nviLampValue. In normal operating
conditions, this value will reflect the
nviLampValue. It may differ if the
heartbeat interval is exceeded and the
defaultLevel differs from the value
in nviLampValue.
nvoLcStatus UNVTfaults
Feeds alarm logs only on change to
minimize the data requirement on the
IP network. The frequency of changes
to this variable is carefully managed
to conserve bytes consumed by data
logs.
nvoVersion UNVTversion
A string describing the version of the
OLC application, such as 1.00.09.
UNVTcontrolData – nvoControlData Details
The LC conserves power line bandwidth by reporting the operating state of the
LC in a single output network variable nvoControlData (UNVTcontrolData),
described in this section. Previous profile designs typically require three poll