Echelon i.LON SmartServer Guía de usuario Pagina 101

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 131
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 100
i.LON SmartServer Power Line Repeating Network Management Guide 87
d. In the Function box, select the Sundown (
) icon. The calculated sundown time appears in
the Time box, which becomes read-only, and an Offset field is added to the dialog. Verify
that the Offset field is set to 00:00.
e. In the Value box, select #UNLOCK.
f. In the Priority box, enter a priority that is lower than the 255 priority used for the weekday
daily schedule (this example use a priority of 220). This priority essentially locks out the
events in the weekday daily schedule, which have lower priorities (255).
g. Click Close to return to the Edit: <exception start date> dialog. The exception schedule is
updated to reflect the lower priority events that are now scheduled to occur after the
#UNLOCK event at sundown.
Vista de pagina 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 130 131

Comentarios a estos manuales

Sin comentarios