The LonPoint Application and Plug-in Guide 6-3
Analog Input
This tab appears as follows:
This tab shows the flow of information through the Analog Input functional
block. It contains the following fields:
Measurement Type Determines whether the input reads voltage (Volts),
current (Amps), or resistance (Ohms). The value in
this field must match the hardware settings on the
associated LonPoint module. See the LonPoint
Hardware and Installation Guide for information on
changing the hardware settings.
Measurement Current If the Measurement Type field is set to Ohms, this
field determines whether a current of 25
µA or 400
µA is used in measuring resistance. If the
Measurement Type field is set to Volts or Amps, this
field is not used.
Input Gain Determines the gain for the input. See Analog Input
Gain and Current Settings later in this chapter for
more information on gain settings.
Measurement Limit Displays a calculation of the highest value that may
be read from the transducer, as determined by the