Echelon LonPoint Application and Plug-In Manual de usuario Pagina 70

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 191
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 69
7-4 Analog Output Functional Block
selected, the input range is 0 to 100%. Input ranging
is useful for split-range applications where a single
value drives multiple actuators, but each actuator is
active over a different input range.
The analog output functional block can be configured
to be reversing (i.e. go from 0% to 100% as the input
goes from 100% to 0%) by switching either the Input
Range or the Output Range values.
Output Range Defines the minimum and maximum range of the
output. The Output Type field determines whether a
current or voltage will be sent to the actuator. These
units must match the hardware jumpers set in the
device (see the LonPoint Module Hardware and
Installation Guide).
Defaults
This tab appears as follows:
This tab sets the default and override values for the analog output functional
block. This tab contains the following fields:
Analog Value Default This value will be used if the
Analog network
variable is not connected or has not received an
update since the last device reset.
Vista de pagina 69
1 2 ... 65 66 67 68 69 70 71 72 73 74 75 ... 190 191

Comentarios a estos manuales

Sin comentarios