146 Timer/Counter Input Models
0.839 s
STOPSTART
t
ret
t
fin
READ
TIMER/
COUNTER
FLAG AND
EVENT
REGISTER
CLEAR FLAG
END OF
io_in()
START OF
io_in()
mux
Event Register
IO10
IO9
IO8
IO0
IO1
IO2
IO3
IO4
IO5
IO6
IO7
System Clock
Divide Chain
Optional Pull-Up Resistors for 3100 Family Devices
Event Register
Timer/Counter 2
Timer/Counter 1
IO11
Figure 54. Pulsecount Input and Timing
Table 55. Pulsecount Input Latency Values for Series 3100 Devices
Symbol Description Typical at 10 MHz
t
fin
Function call to input sample 86 μs
t
ret
Return from function 52 μs or 22 μs
Note: If the measurement is new, t
ret
= 52 μs. If a new time is not being
returned, t
ret
= 22 μs.
Programming Considerations
For pulsecount input, the data type of the return value for the io_in( ) function is
an unsigned long.