Echelon SmartServer 2.2 Manual de usuario Pagina 190

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 560
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 189
SmartServer 2.2 User’s Guide 191
2. Configure the following properties:
SOAP Timeout
Set the maximum period of time (in seconds) that the SmartServer waits for
a response to a SOAP request before the transaction is canceled and a
timeout error is reported. The default timeout is 120 seconds.
Polling
Set how frequently (in seconds) the SmartServers built-in Web pages poll
the SmartServers internal data server for data point updates. The default
poll rate is 1 second. Select the Disable check box to disable the polling of
data points by the SmartServers built-in Web pages.
You can use this property to adjust the amount of LAN/WAN traffic that is
generated by the SmartServers built-in Web pages.
Max Age of Data
Point Values
Set the maximum period of time (in seconds) that data point values are
cached in the SmartServers internal data server before it polls the data
points and returns updated values to the SmartServers built-in Web pages.
This enables you to control the amount of traffic that is generated on a
specific channel by the SmartServers built-in Web pages. If you enable this
option, the default maximum age is 0.5 seconds.
The SmartServer compares the Maximum Age value to the amount of time
a data point value has been cached in its internal data server, and then does
the following:
If Maximum Age is less than the period of time the data point value has
been cached, the SmartServers internal data server polls the data point
and returns the updated value to the SmartServers built-in Web pages.
If Maximum Age is greater than the period of time the data point value
has been cached, the SmartServers internal data server returns the
cached value to the SmartServers built-in Web pages.
If Maximum Age is set to 0, the SmartServers internal data server
polls the data point and returns the updated value to the SmartServers
built-in Web pages regardless how current the data point is. This is the
default value if the Maximum Age option is enabled.
Vista de pagina 189