Echelon SmartServer 2.2 Manual de usuario Pagina 484

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 560
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 483
SmartServer 2.2 User’s Guide 485
3. Set the following synchronization options:
Synchronize All Internal
SmartServer Items
Synchronizes all internal items in the SmartServers
internal database, including hidden items, with the
OpenLNS network database.
Internal items include the following:
LONWORKS channels.
The SmartServers internal App device and its
child functional blocks and data points.
The SmartServers internal IP-852 router.
Custom app devices and their child functional
blocks and data points.
Selecting this option also transmits changes made to
the LON driver properties of the internal items in the
SmartServer tree to the OpenLNS network database,
and it updates the SmartServers internal database with
changes made to the LON driver properties of the
internal items with OpenLNS CT, OpenLNS tree, or
other OpenLNS application.
This option is cleared by default, which means that the
SmartServer sends only changes made to the internal
items in the SmartServer tree to the OpenLNS network
database. In addition, the SmartServers internal
database is updated only with the following changes
made to internal items with OpenLNS CT:
Renaming of devices or functional blocks.
Addition of functional blocks to the SmartServers
internal App device that have stencils with no
dynamic network variables on them.
Deletion of the SmartServer App devices
functional blocks.
Addition or deletion of dynamic network variables
Vista de pagina 483
1 2 ... 479 480 481 482 483 484 485 486 487 488 489 ... 559 560

Comentarios a estos manuales

Sin comentarios