Echelon SmartServer 2.2 Manual de usuario Pagina 264

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 560
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 263
SmartServer 2.2 User’s Guide 265
You can change the default presets for a given data type by modifying its
template in the /config/template/lonworks/dp folder on the SmartServer
flash disk. For example, you could change the default presets for the
SNVT_switch data type by modifying the
/config/template/lonworks/dp/#0000000000000000.SNVT_switch.xml
file.
Fields
Structured data points (data points with multiple fields) such as
SNVT_switch, SNVT_alarm, and SCPT_maxRcvT have default names
and unit strings describing each field that are defined by resource files.
You can edit the default names and unit strings.
Using a SNVT_swtich data point for example, the data point will have
fields named by default Value and State with unit strings of % of full
level and state code, respectively. You could change the unit string
used to describe the State field from the default state code to
occupied for a restroom occupancy sensor
To edit the unit strings of the fields within a structured data point on an
internal SmartServer device, click Add Unit to open the Select Fields
dialog. Click the field with the unit string to be edited and then click OK
to return to the Configure - Data Point Web Page, and then click Submit.
The selected field is added under the Fields property at the bottom of the
Configure - Data Point Web Page. You can then enter a brief description
of the unit string to be used for that field in the Unit String box.
To edit the unit strings of the fields within a structured data point on an
external device, enter a brief description of the units to be used for that
field in the Unit String box.
To reset the unit string used by a field to its default, click the field and
then click Delete Unit.
5. Click Submit.
Configuring LONWORKS Data Point Driver Properties
To configure the driver properties of a data point, follow these steps:
1. Click Driver.
2. Click one or more data points to be configured.
3. The Setup - LON Data Point Driver Web page opens.
Vista de pagina 263