274 Using the SmartServer as Network Management Tool
Berndt Contec LAE Electronic LCD 15*
Cummins MOD-LON
Dixel XW570K
Honeywell 7800 series Burner controls with an S7810M Modbus Interface module
Leibert system 3 AHU with and OpenComms interface module
Schneider PM500*
Socomec A40*
Veris Industries H8035 Modbus Enercept kW/kWh meter
Wago System 750*
Yaskawa E7
* Device has a pre-defined template file loaded on the SmartServer which you can use to add it to the
SmartServer. See Using Device Templates in Chapter 4 for more information.
Each Modbus TCP/IP slave device must be added to a separate channel. Adding more than one
Modbus TCP device to a Modbus TCP/IP channel generates unexpected results such as all points
being mapped to the first device defined on the channel. These errors occur even if the Modbus
TCP/IP addresses are unique.
Creating Modbus Devices
To create a Modbus device, follow these steps:
1. Right-click a Modbus channel, and then select Add Device on the shortcut menu.
2. The Add Device dialog opens.